banner

BKDR Type Anti-vibration Rubber Mounts

Short Description:

 The simple structure of the BKDR rubber mount make it easy to install.
 With the nature rubber, it has a high deflection while the frequency of the vibration is under 15Hz (900RPM).
 The load range from 200kg to 1200kg.
 It’s widely use in heating, air-conditioning, pumps, fans, compressor, control cabinet.


Product Detail

Product Tags

Description

The BKDR type rubber mounts provides effective vibration control for use directly under HVAC, power generation and electrical equipment in conjunction with the equipment’s mounting holes.

The BKDR type rubber mounts have a steel baseplate with mounting holes and a threaded insert at the top of the isolator for attaching to equipment. All metal parts are completely embedded in the elastomeric material.

Three different rubber hardness shore A 40 to 75 offer a load capacity range of 10 to 1200kg per isolator, offering isolators that may be accurately selected for the equipment weight.

These rubber mounts’ resilience and their broad range of different sizes and dimensions allow these mounts to be used in many applications that require noise and vibration isolation.

Features

● The simple structure of the BKDR rubber mount make it easy to install.
● Natural rubber has superior resistance to tears and abrasion as well as good flexibility in cold temperatures.
● With the nature rubber, it has a high deflection while the frequency of the vibration is under 15Hz (900RPM).
● Static load range of 10 to 1200kg, offers solutions for a wide range of equipment weights.
● It’s widely use in heating, air-conditioning, pumps, fans, compressor, control cabinet.
● Ribbed isolator base provides a non-skid surface.
● Tapped bolt holes in top of the isolator permit attachment to the equipment and the addition of leveling bolts.
● Mounting bolts are not provided.

微信图片_20221027153520

Applications

Air conditioning units, Fans
Pumps, Chillers
Air compressors, HVAC equipment
Textile machine

Product Parameter

图片26

Type

A

B

C

D

E

F

L

Maximum Compression (mm)

Maximum Load (kg)

40 degrees

60 degrees

75 degrees

BKDR-1

30

38

M8

M8

81

41

60

4

12

25

30

BKDR-2

44

48

M10

M10

98

59

76

4

30

60

80

BKDR-3

60

71

M12

M10

143

86

105

6

70

120

180

BKDR-5

108

60

M16

M12

212

132

165

10

400

800

 1200